Below is a step-by-step troubleshooting and maintenance guide for the Pro Air 20 and Pro Air 60 Aeration Systems.
Step 1 – Start at the Compressor (Top of System)
- If no air is reaching the diffusers, always begin troubleshooting at the compressor.
- Locate the air discharge valve/manifold on the compressor.
- Using a screwdriver:
- Loosen the clamp.
- Remove the airline tubing.
- Check for airflow directly from the compressor outlet.
- What to look for:
- Strong airflow present: Compressor is functioning → proceed to Step 2.
- Weak or no airflow: Likely diaphragm issue → skip to Step 5.
Step 2 – Inspect the Check Valve Orientation
- The check valve ensures air flows toward the pond and prevents water from backing into the compressor.
- Locate the check valve inline with the tubing.
- Remove it if necessary.
- Blow through the valve to confirm airflow direction.
- Correct condition:
- Air should pass only in the direction of the diffuser.
- Common issue:
- Installed backwards → blocks airflow completely.
- Action:
- Reinstall in the correct direction if needed.
- Action:
- Installed backwards → blocks airflow completely.
- Correct condition:
Step 3 – Inspect Airline Tubing
- Move downstream through the system.
- Check the entire length of tubing for:
- Kinks
- Pinches
- Crushing or deformation
- Blockages
Action:
- Straighten or replace damaged tubing as needed.
Step 4 – Check Airflow at the Diffuser
- The diffuser is typically low maintenance but should still be verified.
- Disconnect tubing at the diffuser (loosen worm gear clamp).
- Check for airflow at the end of the airline.
What to expect:
- Strong airflow reaching the diffuser.
Notes on diffuser design:
- Made of EPDM rubber membrane with microscopic pores.
- Self-cleaning:
- Air pressure expands membrane.
- Debris is pushed out during operation.
- If airflow is present but performance is poor:
- Reconnect and observe bubbles in pond.
- Minimal maintenance typically required.
Step 5 – Diagnose Compressor Diaphragm (If Low/No Air at Source)
- If little or no air is coming directly from the compressor:
Likely cause:
- Worn or failed diaphragm inside the compressor.
Important context:
- Diaphragms wear over time (similar to tires).
- Wear rate depends on:
- Temperature (hot environments accelerate wear)
- Dust and debris
- Runtime and general use
Step 6 – Replace Diaphragm and Air Filter
Use only the diaphragm and air filter replacement kit from Aquascape.
Procedure:
- Remove 4 screws from compressor housing.
- Lift off the top cover.
- Remove 4 screws from diaphragm cover.
- Gently pull off diaphragm cover.
- Remove the silver plate (keep gasket intact).
- Inspect plastic diaphragm chamber:
- Replace if damaged.
- Loosen center screw of diaphragm assembly.
- Remove diaphragm housing.
- Separate internal plastic components.
- Install new rubber diaphragm:
- Ensure all components are included:
- Thin washers
- Internal parts
- Ensure all components are included:
- Reassemble in reverse order:
- Secure diaphragm housing
- Reinstall cover and screws
Step 7 – Final System Check
- After reassembly:
- Reconnect all tubing.
- Ensure:
- Check valve is properly oriented
- Tubing is secure and unkinked
- Power on the unit.
- Verify:
- Strong airflow at compressor
- Consistent bubbling at diffuser
Key Maintenance Takeaways
- Always troubleshoot from the compressor down to the diffuser.
- The most common failure point is the diaphragm.
- Diffusers require minimal maintenance due to self-cleaning design.
- Routine inspection helps prevent performance loss.